EasyManuals Logo

LG Multi V CRUN Series User Manual

LG Multi V CRUN Series
249 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #224 background imageLoading...
Page #224 background image
224 Trouble Shooting Guide
Self-diagnosis function
No
No
Execute automatic
addressing
Transmission
error in all of
indoor units?
Does it execute
automatic
addressing?
Yes
Yes
Is the state of
transmission in
outdoor unit
normal?
Yes
Check and replace
indoor unit PCB
Is the state of
connection for
transmission
is normal?
No
Yes
Repair the
connection
No
Check and replace
outdoor unit PCB
Repair the
connection
Fault diagnosis and Trouble shooting guide
Outdoor unit
indoor unit
transmission
error
05
Automatic addressing problem.
Unplugging of transmission connector
Misconnection or open of transmission cable
Malfunction of indoor unit transmission circuit
Malfunction of outdoor unit transmission circuit
The distance between power cable and
transmission cable is not enough.
In the case that indoor unit
can not receive any signal
from outdoor unit
successively for 3minutes
Trouble shooting Flow
In indoor unit which
displays error code
Yes
Title
Display
code
Cause of errorMeaning

Table of Contents

Other manuals for LG Multi V CRUN Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG Multi V CRUN Series and is the answer not in the manual?

LG Multi V CRUN Series Specifications

General IconGeneral
BrandLG
ModelMulti V CRUN Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals