Fault diagnosis and Trouble shooting guide
Title
Display
code
Cause of errorMeaning
No
Is the transmission
line connection /
Connector normal?
Yes
Is the transmission
circuit of main PCB
normal?
Yes
Check and Replace the
main PCB
No
Check and replace the
inverter PCB
Repair the connection /
connector
Transmission
error from
indoor unit to
main PCB in
the outdoor
unit
53
• The connector for transmission disconnected
• The transmission line is misconnected or shorted
• Transmission circuit of main PCB is abnormal
• Transmission circuit of indoor unit PCB is
abnormal
In the case that main PCB
can not receive any signal
from indoor unit
successively for 3minutes
Trouble shooting Flow