Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
COMM2: Octet comm. address
103 072
1 0 254 Fig. 3-14, (p. 3-19)
[spacer]
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be selected
for both addresses.
“ASDU”: Application Service Data Unit
[spacer]
COMM2: Name of manufacturer
103 161
1: SE Fig. 3-14, (p. 3-19)
[spacer]
Setting for the name of the manufacturer.
Note: This setting can be changed to ensure compatibility.
[spacer]
COMM2: Octet address ASDU
103 073
1 0 255 Fig. 3-14, (p. 3-19)
[spacer]
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be selected
for both addresses.
“ASDU”: Application Service Data Unit
[spacer]
COMM2: Spontan. sig. enable
103 177
0: None Fig. 3-14, (p. 3-19)
[spacer]
Enable for the transmission of spontaneous signals via the communication
interface.
[spacer]
COMM2: Select. spontan.sig.
103 179
060 000: MAIN: Without function Fig. 3-14, (p. 3-19)
[spacer]
Selection of spontaneous signals for transmission via communication interface 2.
[spacer]
COMM2: Transm.enab.cycl.dat
103 074
0: Without Fig. 3-14, (p. 3-19)
[spacer]
Enable for the cyclic transmission of measured values via the communication
interface.
[spacer]
COMM2: Cycl. data ILS tel.
103 175
060 000: MAIN: Without function Fig. 3-14, (p. 3-19)
[spacer]
Selection of the measured values transmitted in a user-defined telegram via the
communication interface.
[spacer]
COMM2: Delta V
103 050
3.0 0.0 15.0 %Vnom Fig. 3-14, (p. 3-19)
[spacer]
A measured voltage value is transmitted via the communication interface if it
differs by the set delta quantity from the last measured value transmitted.
P631
7 Settings
7-28 P631/EN M/R-11-C // P631-310-650