Parameter Address
Default Min Max Unit Logic Diagram
Limit value
monitoring
LIMIT: General enable USER
014 010
0: No Fig. 3-136, (p. 3-168)
[spacer]
Disabling or enabling limit value monitoring.
[spacer]
LIMIT: IDC,lin>
014 110
Blocked 0.100 1.100 IDC,nom Fig. 3-136, (p. 3-168)
[spacer]
Setting for the operate value IDC,lin> for monitoring the linearized direct
current.
[spacer]
LIMIT: IDC,lin>>
014 111
Blocked 0.100 1.100 IDC,nom Fig. 3-136, (p. 3-168)
[spacer]
Setting for the operate value IDC,lin>> for monitoring the linearized direct
current.
[spacer]
LIMIT: tIDC,lin>
014 112
Blocked 0.00 20.00 s Fig. 3-136, (p. 3-168)
[spacer]
Setting for the operate delay of overcurrent stage IDC,lin>.
[spacer]
LIMIT: tIDC,lin>>
014 113
Blocked 0.00 20.00 s Fig. 3-136, (p. 3-168)
[spacer]
Setting for the operate delay of overcurrent stage IDC,lin>>.
[spacer]
LIMIT: IDC,lin<
014 114
Blocked 0.100 1.100 IDC,nom Fig. 3-136, (p. 3-168)
[spacer]
Setting for the operate value IDC,lin< for monitoring the linearized direct
current.
[spacer]
LIMIT: IDC,lin<<
014 115
Blocked 0.100 1.100 IDC,nom Fig. 3-136, (p. 3-168)
[spacer]
Setting for the operate value IDC,lin<< for monitoring the linearized direct
current.
[spacer]
LIMIT: tIDC,lin<
014 116
Blocked 0.00 20.00 s Fig. 3-136, (p. 3-168)
[spacer]
Setting for the operate delay of undercurrent stage IDC,lin<.
[spacer]
LIMIT: tIDC,lin<<
014 117
Blocked 0.00 20.00 s Fig. 3-136, (p. 3-168)
[spacer]
Setting for the operate delay of undercurrent stage IDC,lin<<.
[spacer]
LIMIT: T>
014 100
200 -20 200 °C Fig. 3-137, (p. 3-169)
[spacer]
Setting for the operate value of temperature monitoring T>.
P631
7 Settings
7-86 P631/EN M/R-11-C // P631-310-650