Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
GSSE: IED view selection
105 170
1: Remote IED
[spacer]
Setting for which GSSE sending device the following statistics information is to
be displayed.
[spacer]
GSSE: IED receiv. messages
105 172
Not measured 0 65535
[spacer]
Counter of the received GSSE telegrams.
[spacer]
GSSE: IED Rx last sequence
105 173
Not measured 0 65535
[spacer]
State of the continuous counter sequence for the message counter received with
each GSSE.
[spacer]
GSSE: IED Rx last message
105 174
Not measured 0 65535
[spacer]
State of the continuous counter sequence for state changes received with each
GSSE.
[spacer]
GSSE: IED missed messages
105 175
Not measured 0 65535
[spacer]
Number of missing GSSE messages (gaps in the continuous sequence
numbering). This counter is reset by GSSE: Reset statistics.
[spacer]
GSSE: IED missed changes
105 176
Not measured 0 65535
[spacer]
Number of missing state changes (gaps in the continuous sequence
numbering). This counter is reset by GSSE: Reset statistics.
[spacer]
GSSE: IED time-outs
105 177
Not measured 0 65535
[spacer]
Number of GSSE received after the validity time period has elapsed.
This counter is reset by GSSE: Reset statistics.
Parameter Address
Default Min Max Unit Logic Diagram
Measured data input
MEASI: Reset Tmax USER
003 045
0: don't execute
[spacer]
Resetting measured maximum temperatures Tmax and Tmax Tx (x=1...9) to
updated measured values.
P631
8 Information and Control Functions
8-86 P631/EN M/R-11-C // P631-310-650