Connecting the Power
20
Power Connection Procedure for JFX600-2513 Machine Number 21
and Later, and the JFX550-2513
• Terminal blocks are attached inside the machine's electrical box.
JFX600-2513JFX600-2513: ×3, JFX550-2513: ×2
A power cable is not included. The user is responsible for providing power cables. Electrical
work between the switchboard and terminal block must be performed by a licensed electrician.
• Be sure to only use the following types of cables and circuit breakers.
(1) Cable: VCT-5.5 mm
2
× 3-core (600 V) or UL-AWG10 × 3C (600 V) or equivalent. Outer
sheath external diameter 16 to 20 mm.
(2) Circuit breaker: Single-phase 200 to 240 V AC, 30 A
l
Wire preparation
1
Strip 60 mm of the sheath from the power cable.
60 mm
*1
Black 1: L
Black 2: N
Green/
Yellow: G
*1: Please prepare the wire according to
the particular crimp terminal
specifications.