12 DATA USED FOR POSITIONING CONTROL
12.7 Monitor Data
[Md.133] Operation cycle over flag
This flag turns ON when the operation cycle time exceeds operation cycle.
Refresh cycle: Immediate
Reading the monitor value
Monitoring is carried out with a decimal display.
Latch status of operation cycle over is indicated. When this flag turns ON, correct the positioning detail or
change the operation cycle longer than current setting.
Buffer memory address
Refer to the following for the buffer memory address in this area.
Page 390 Monitor data
[Md.134] Operation time
Stores the time that took for operation every operation cycle.
Refresh cycle: Operation cycle
Reading the monitor value
Monitoring is carried out with a decimal display.
Buffer memory address
Refer to the following for the buffer memory address in this area.
Page 390 Monitor data
[Md.135] Maximum operation time
Stores the maximum value of operation time after each module's power supply ON.
Refresh cycle: Immediate
Reading the monitor value
Monitoring is carried out with a decimal display.
Buffer memory address
Refer to the following for the buffer memory address in this area.
Page 390 Monitor data
Storage value
0: OFF
1: ON (Operation cycle over occurred.)
Monitor
value
Storage value
Unit: μs
Monitor
value
Storage value
Unit: μs
Monitor
value