11.8.2 [Function switching] switching of allocation and functions of input terminals
When the counters C248, C253 and C254 are combined with the following special auxiliary relays, the
allocation of the input terminals and functions are changed.
Program the special auxiliary relays just before the counters.
Counter No. Function switching method Details of change
C248(OP) • Reset input is not given.
C253(OP) • Reset input is not given.
C254(OP)
• The input count (2-phase 2-count) changes as follows
Phase A : Changes from X000 to X006.
Phase B : Changes from X001 to X007.
• Reset input is not given.
• Start input is not given.
M8388
M8392
C248
K
M8388
M8392
C253
K
M8388
M8395
C254
K