8.5 Procedures for Installing Directly (with M4 Screws)
The product can be installed directly in the enclosure (with screws).
Point
Position the holes so that there is a gap of 1 to 2 mm (0.04" to 0.08") between the products.
8.5.1 Hole pitches for direct mounting
The product mounting hole pitches are shown below.
For the pitch that varies depending on the product, refer to the table.
1. Main unit (A)
Unit: mm (inches)
2. Special adapter (B)
Unit: mm (inches)
3. Input/output powered extension unit(C or D)
Unit: mm (inches)
Model name Mounting hole pitch(W)
A
FX
3G-14MT/ES 82 (3.23")
FX
3G-24MT/ES 82 (3.23")
FX
3G-40MT/ES 122 (4.81")
FX
3G-60MT/ES 167 (6.58")
Model name Mounting hole pitch(W)
B
FX3U-4AD-ADP
FX3U-4DA-ADP
FX3U-4AD-PT-ADP
FX3U-4AD-PTW-ADP
FX3U-4AD-PNK-ADP
FX3U-4AD-TC-ADP
FX3U-232ADP(-MB)
FX
3U-485ADP(-MB)
Refer to the figure shown
left.
Model name Mounting hole pitch(W)
C
FX
2N-32ER-ES/UL
FX
2N-32ET-ESS/UL
FX2N-32ER
FX2N-32ET
FX2N-32ES
140 (5.52")
D
FX2N-48ER-ES/UL
FX2N-48ET-ESS/UL
FX2N-48ER
FX2N-48ET
172 (6.78")
FX2N-48ER-UA1/UL 210 (8.27")
W
A
4(0.16")
82 (3.23")
90 (3.55")
4(0.16")
4(0.16")
B
98 (3.86")
15.1
(0.6")
2.5
(0.1")
105 (4.14")
5
(0.2")
C
W
80 (3.15")
90 (3.55")
D
W
80 (3.15")
90 (3.55")
5
(0.2")
5
(0.2")
5
(0.2")