14 Test Operation, Adjustment, Maintenance and Troubleshooting
14.4 Maintenance and Periodic Inspection
174
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
2. Lamp load
Lamp loads generally generate rush current 10 to 15 times the stationary current. Make sure that the rush
current does not exceed the current corresponding to the maximum specified resistance load.
3. Capacitive load
Capacitive loads can generate rush current 20 to 40 times the stationary current. Make sure that the rush
current does not exceed the current corresponding to the maximum specified resistance load. Capacitive
loads such as capacitors may be present in electronic circuit loads including inverters.
* About the maximum load specifications of the resistance load, refer to the specification for each model.
For specifications on the input/output powered extension units, refer to Chapter 15.
For specifications on the input/output extension blocks, refer to Chapter 16.
For specifications on the terminal block, refer to Chapter 20.

Table of Contents

Other manuals for Mitsubishi FX3G Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3G Series and is the answer not in the manual?

Mitsubishi FX3G Series Specifications

General IconGeneral
ModelFX3G Series
Power SupplyAC 100-240V or DC 24V
Program Capacity32, 000 steps
Execution Speed0.21 µs/basic instruction
Communication OptionsRS-422, USB, Ethernet
Expansion ModulesAnalog, digital, communication
Programming LanguageLadder Logic, Instruction List
Built-in FunctionsHigh-speed counters, pulse output
Analog I/OAvailable via expansion modules

Related product manuals