28 Rev. 01/2015
6.1 Input and Output Wiring on the Controller
Operational safety!
All connector screws and screw joints must be adequately tightened.
Compliance with the following tightening torques is mandatory:
RS232 connection: 1 Nm (0.7 lb-ft)
Connection plug 6-pole, 7-pole, 10-pole: 2.6 Nm (1.9 lb-ft)
Connection plug 14-pole, 19-pole: 5 Nm (3.7 lb-ft)
Operational safety!
Never connect more than one output to each ignition coil, as the output
boards can otherwise be damaged!
Assignment of the wire colors
Take the assignment of the wire colors of the wiring harness for the input
and output wiring from the wiring plan enclosed with the wiring harness.
Protection when using wiring rails
Every wiring rail on the engine block should be grounded to avoid
disruptions in the device caused by secondary current in the ignition coils.
6 WIRING OF THE DEVICE