Page #118 background imageLoading...
Page #118 background image
ioThinx 4510 Series Appendix
A-14
Topic Description Category Trigger
{deviceName}/read/{ioName}/diCounterValue DI - Counter mode -
value
value Interval
{deviceName}/read/{ioName}/diCounterOverflow
Flag
DI - Counter mode -
overflow flag (0:
Normal, 1: Overflow)
attribute Interval
{deviceName}/read/{ioName}/diCounterOverflow
FlagClear
DI - Counter mode -
clear overflow flag (1:
Clear)
attribute Interval
{deviceName}/read/{ioName}/diCounterStatus DI - Counter mode -
status (0: pause, 1:
run)
value both
(OnChange)
{deviceName}/read/{ioName}/doMode DO - mode (0: DO, 1:
Pulse)
attribute Interval
{deviceName}/read/{ioName}/doStatus DO - status (0: OFF,
1: ON)
value both
(OnChange)
{deviceName}/read/{ioName}/doPulseCount DO - Pulse mode -
count
attribute Interval
{deviceName}/read/{ioName}/doPulseOnWidth DO - Pulse mode - ON
width (unit: 500us)
attribute Interval
{deviceName}/read/{ioName}/doPulseOffWidth DO - Pulse mode -
OFF
width (unit: 500us)
attribute Interval
{deviceName}/read/{ioName}/doPulseStatus DO - Pulse mode -
status (0: Stop 1:
Start)
value both
(OnChange)
{deviceName}/read/{ioName}/relayTotalCount Relay - total count attribute Interval
{deviceName}/read/{ioName}/relayCurrentCount Relay - current count value Interval
{deviceName}/read/{ioName}/relayCurrentCount
Reset
Relay - reset current
count (1: Reset)
attribute Interval
{deviceName}/read/{ioName}/relayStatus Relay - Relay mode -
status (0: OFF, 1: ON)
value both
(OnChange)
{deviceName}/read/{ioName}/aiMode AI - mode (0: disable
1: 0-10 V, 2: 0-20
mA, 3: 4-20 mA
burnout, 4: 4-20 mA,
5: ±10 V)
attribute Interval
{deviceName}/read/{ioName}/aiValueRaw AI - raw value attribute Interval
{deviceName}/read/{ioName}/aiValueRawMin AI - minimum raw
value
attribute Interval
{deviceName}/read/{ioName}/aiValueRawMax AI - maximum raw
value
attribute Interval
{deviceName}/read/{ioName}/aiResetMinValue AI - reset minimum
value (1: Reset)
attribute Interval
{deviceName}/read/{ioName}/aiResetMaxValue AI - reset maximum
value (1: Reset)
attribute Interval
{deviceName}/read/{ioName}/aiStatus AI - status (0: normal,
1: burnout, 2: over
range, 3. under range)
value both
(OnChange)
{deviceName}/read/{ioName}/aiBurnoutValueSc
aled
AI - scaled burnout
value
attribute Interval
{deviceName}/read/{ioName}/aiValueScaled AI - scaled value value both (interval)
{deviceName}/read/{ioName}/aiValueScaledMin AI - minimum scaled
value
attribute Interval

Table of Contents

Other manuals for Moxa Technologies ioThinx 4510 Series