ioThinx 4510 Series Appendix
A-15
Topic Description Category Trigger
{deviceName}/read/{ioName}/aiValueScaledMax AI - maximum scaled
value
attribute Interval
{deviceName}/read/{ioName}/aoMode AO - mode (0:
Disable, 1: 0-10 V, 2:
0-20mA, 3: 4-20 mA)
attribute Interval
{deviceName}/read/{ioName}/aoValueRaw AO - raw value attribute Interval
{deviceName}/read/{ioName}/aoValueScaled AO - scaled value value both (interval)
{deviceName}/read/{ioName}/aoStatus AO status (0:
Normal, 1: Fault)
value both
(OnChange)
{deviceName}/read/{ioName}/rtdStatus RTD - Status (0:
normal, 1: burnout)
value both
(OnChange)
{deviceName}/read/{ioName}/rtdMode RTD - Type (0: PT50,
1: PT100, 2: PT200, 3:
PT500, 4: PT1000; 14:
310 Ohm, 15: 620
Ohm, 16: 1250 Ohm,
17: 2200 Ohm; 20:
JPT100, 21: JPT200,
22: JPT500, 23:
JPT1000; 30: NI100,
31: NI200, 32: NI500,
33: NI1000, 34:
NI120, 50: disable)
attribute Interval
{deviceName}/read/{ioName}/rtdValueScaled RTD - scaled value value both (interval)
{deviceName}/read/{ioName}/rtdValueScaledMin RTD - minimum scaled
value
attribute Interval
{deviceName}/read/{ioName}/rtdValueScaledMa
x
RTD - maximum
scaled value
attribute Interval
{deviceName}/read/{ioName}/rtdResetMinValue RTD - reset minimum
value (1: RESET)
attribute Interval
{deviceName}/read/{ioName}/rtdResetMaxValue RTD - reset maximum
value (1: RESET)
attribute Interval
{deviceName}/read/{ioName}/tcStatus TC - Status (0:
normal, 1: burnout)
value both
(OnChange)
{deviceName}/read/{ioName}/tcType TC - Type (0: J Type,
1: K Type, 2: T Type,
3: E Type, 4: R Type,
5: S Type, 6: B Type,
7: N Type, 14:
±78.126 mV, 15:
±39.062 mV, 16:
±19.532 mV, 50:
disable)
attribute Interval
{deviceName}/read/{ioName}/tcValueScaled TC - scaled value value both (interval)
{deviceName}/read/{ioName}/tcValueScaledMin TC - minimum scaled
value
attribute Interval
{deviceName}/read/{ioName}/tcValueScaledMax TC - maximum scaled
value
attribute Interval
{deviceName}/read/{ioName}/tcResetMinValue TC - reset minimum
value (1: RESET)
attribute Interval
{deviceName}/read/{ioName}/tcResetMaxValue TC - reset maximum
value (1: RESET)
attribute Interval

Table of Contents

Other manuals for Moxa Technologies ioThinx 4510 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioThinx 4510 Series and is the answer not in the manual?

Moxa Technologies ioThinx 4510 Series Specifications

General IconGeneral
BrandMoxa Technologies
ModelioThinx 4510 Series
CategoryController
LanguageEnglish