9 Operation
Maschinenfabrik Reinhausen GmbH 2022 1278595028/00 EN TAPCON
®
250
Delay time
You can use this parameter to set the delay time in order to delay the issuing
of the event message.
Reaction
You can use this parameter to set the behavior of the device if the measured
value is higher than the upper limit (> or >>) or lower than the lower limit (<
or <<). You can select the following options:
Setting Behavior
Off No reaction.
Auto blocking Automatic regulation is blocked.
You can continue to perform tap-change operations in
manual mode.
Auto/manual blocking Automatic regulation is blocked.
You cannot perform tap-change operations in manual
mode.
Table36: Behavior when an event message is issued
9.2.4 Power monitoring
For monitoring the transformer's current power, you can set the following
limit values:
Measured value Lower
limit2
Lower
limit1
Upper
limit1
Upper
limit2
Apparent power S<< S< S> S>>
Active power P<< P< P> P>>
Reactive power Q<< Q< Q> Q>>
Power factor (amount) |cosφ|<< |cosφ|< -
-
Table37: Limit values for power monitoring
1. Go to Settings > Parameters > Grid > Power monitoring.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the Accept button to save the modified parameter.
You can set additional parameters for each limit value:
Absolute
You can use this parameter to specify a limit value.

Table of Contents

Other manuals for MR TAPCON 250

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the MR TAPCON 250 and is the answer not in the manual?

MR TAPCON 250 Specifications

General IconGeneral
BrandMR
ModelTAPCON 250
CategoryController
LanguageEnglish

Related product manuals