9 Operation
Maschinenfabrik Reinhausen GmbH 2022166 8595028/00 ENTAPCON
®
250
9.5 Motor-drive unit and control cabinet
9.5.1 Control of the motor-drive unit
The following parameters let you configure control of the motor-drive unit.
You can set the following:
Switching pulse
Motor runtime
Switching direction
Figure85: Motor control unit
Go to Settings > Parameters > Motor and control cabinet > Torque
monitoring .
9.5.1.1 Setting the switching pulse for controlling the motor-drive unit
You can use the parameters Switching pulse type, Switching pulse time and
Switching pulse pause to adapt the device switching pulse to the require-
ments of the motor-drive unit controller.
1. Go to Settings > Parameters > Motor and control cabinet > Motor
control.
2. Select the desired parameter.
3. Set the parameter.
4. Press the Accept button to save the modified parameter.
Switching pulse type
You can use this parameter to toggle the switching pulse between a continu-
ous pulse or a time-controlled switching pulse.