9 Operation
Maschinenfabrik Reinhausen GmbH 2022 1318595028/00 EN TAPCON
®
250
9.2.6 Monitoring settings
Monitoring U < 30V
You can use this parameter to activate events and function monitoring. You
can select the following options:
Setting Behavior
Activate Monitoring is activated, even if the measured voltage
U > 30 V.
Deactivate Monitoring is activated. Between 19 V < U < 30 V, the
following monitoring processes are suppressed:
Voltage monitoring
Power monitoring
Power flow monitoring
Function monitoring
Table40: Activate function monitoring
9.2.7 TAPCON® 2xx retrofit
The TAPCON® 2xx retrofit function allows you to operate the device in par-
allel operation with existing devices. Parallel operation with the following ex-
isting devices is supported:
TAPCON®230 pro/expert up to year of construction 2021-08
TAPCON®240
TAPCON®250 predecessor device up to year of construction 2022-06
TAPCON®260
TRAFOGUARD® with "Voltage regulation" options package