9 Operation
Maschinenfabrik Reinhausen GmbH 2022 978595028/00 EN TAPCON
®
250
Unsolicited messages
You can use this parameter to set whether the device is to support unso-
licited messages. If you activate unsolicited messages, the device sends a
message via the control system every time a value is changed.
Repetition of unsolicited messages
You can use this parameter to set how often the device is to send an unso-
licited message until it receives a response from the DNP3 master.
Timeout
You can use this parameter to set the timeout for unsolicited messages.
Timeout for response confirmation
You can use this parameter to set the timeout for response confirmation for
unsolicited messages.
9.1.7 Setting the measured value recorder
Depending on the set average value interval, the measured value recorder
can display the measured values over a shorter or longer time period:
Average value interval = 1s: approx. 1day and 8hours
Average value interval = 86,400s (= 24h): approx. 315years