9 Operation
Maschinenfabrik Reinhausen GmbH 2022 1298595028/00 EN TAPCON
®
250
9.2.5 Power flow monitoring
A reversal of power flow occurs if the active power is negative. You can set
the following parameters for this:
Hysteresis
Delay time
Behavior
1. Go to Settings > Parameters > Grid > Power flow monitoring.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the Accept button to save the modified parameter.
Hysteresis
You can use this parameter to set the hysteresis. You can use this to avoid
the unnecessary generation of messages if the measured value fluctuates
around a threshold value.
Delay time
You can use this parameter to set the delay time in order to delay the issuing
of the event message.