9 Operation
Maschinenfabrik Reinhausen GmbH 2022154 8595028/00 ENTAPCON
®
250
Function monitoring
You can use this parameter to activate function monitoring. When doing so,
also observe the monitoring settings [Page 131].
You can select the following options:
Setting Behavior
Off Function monitoring is deactivated.
Only Auto Function monitoring is only active in AVR AUTO oper-
ating mode.
Auto and Manual Function monitoring is active in AVR AUTO and AVR
MANUAL operating modes
Table44: Activate function monitoring
Hysteresis
You can use this parameter to set the hysteresis. You can use this to avoid
the unnecessary generation of messages if the measured value fluctuates
around a threshold value.
Delay time
You can use this parameter to set the delay time in order to delay the issuing
of the event message.