8 Commissioning
Maschinenfabrik Reinhausen GmbH 202282 8595028/00 ENTAPCON
®
250
3. Compare the tap position displays of master and follower . All de-
vices must display the same tap position. If this is not the case, switch all
devices to the same tap position.
Figure55: Comparing the tap position
1 Master 3 Tap position display
2 Follower
4. Press on the follower to select manual mode.
5. If necessary, set the follower tapping direction.
6. Press on the master to select manual mode.
7. Press or on the master to manually change the tap position.
8. Press on the follower to select auto mode.
ð The follower switches to the same tap position as the master.
9. Press on the master to select auto mode.
10. Press on the follower to select manual mode.
11. Press or on the follower to manually change the tap posi-
tion.
ð After expiration of the set delay time for parallel operation errors
[Page 153], there is a tap difference from the follower to the master.
12. Press several times on the follower to manually increase the tap
position by the number of permitted steps ("Maximum permitted tap dif-
ference") and then one further step.
ð After expiration of the set delay time for parallel operation errors, there
is a tap difference to follower on the master.
ð After expiration of the set delay time for parallel operation errors, there
is a tap difference to master on the follower.
13. Press on the follower to select auto mode.
ð There is no response. All devices remain blocked.