9 Operation
Maschinenfabrik Reinhausen GmbH 2022 858595028/00 EN TAPCON
®
250
Setting Description
Hardware only The device accepts commands through digital inputs.
SCADA only The device accepts commands via SCADA.
Hardware and SCADA The device accepts commands via digital inputs and
SCADA.
Table14: Selecting remote behavior
9.1.1.2 Set up automatic logout
You can change the settings so that the device of a logged-in user automati-
cally logs the user out after a certain period of inactivity.
These settings apply to all users. If you have activated the Auto login func-
tion for a user, then this user will not be automatically logged out.
1. Go to Settings > Parameters > System > General.
2. Select the desired parameter.
3. Set the parameter.
4. Press the Accept button to save the modified parameter.
Auto logout
You can use this parameter to activate th automatic logout function.
Time until auto logout
You can use this parameter to set the time period of inactivity after which a
user is automatically logged out.
9.1.1.3 Activating/deactivating service user access
The device is equipped with user access for the Maschinenfabrik Rein-
hausen GmbH Technical Service department. This access is for error diag-
nostics and troubleshooting in the event of device faults.
You can use this parameter to activate or deactivate service user access. To
safeguard IT security, only activate service user access for a limited time pe-
riod for remedying faults.