XPS Unified Programmer’s Manual
7.2.1.143 PositionerBacklashDisable
Name
PositionerBacklashDisable Disables the backlash compensation.
Input tests
- Refer to section 7.1: “Input Tests Common to all XPS Functions”.
- Checks the positioner type (must not be a secondary positioner): (-8)
Description
This function disables the backlash compensation.
In the “stages.ini” file the parameter “Backlash” will enable or disable this feature as
follows:
Backlash = 0 >Disable backlash
Backlash >0 >Enable backlash
NOTE
The backlash compensation is not allowed with a secondary positioner (gantry
mode).
The backlash must be disabled to execute a trajectory, use a jog mode or analog
tracking mode.
Prototype
int PositionerBacklashDisable(
int SocketID,
char * FullPositionerName
)
Input parameters
SocketID int Socket identifier gets by the
“TCP_ConnectToServer” function.
FullPositionerName char * Positioner name.
Output parameters
None.
Return (In addition to the results of “Input Tests Common to all XPS
Functions”)
0: No error.
-8: Wrong object type for this command.
EDH0373En1023 01/18 220

Table of Contents

Other manuals for Newport XPS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Newport XPS and is the answer not in the manual?

Newport XPS Specifications

General IconGeneral
Controller TypeMulti-axis motion controller
Power Supply24 VDC
Communication InterfaceEthernet
Programming LanguageC, C++, .NET, LabVIEW
Supported Motor TypesStepper
Operating System CompatibilityWindows
AxesUp to 8 axes

Related product manuals