XPS Unified Programmer’s Manual
7.2.1.269 PositionerPositionCompareAquadBPrescalerGet
Name
PositionerPositionCompareAquadBPrescalerGetGets PCO AquadB interpolation
factor.
Input tests
- Refer to section 7.1: “Input Tests Common to all XPS Functions”.
- Checks encoder type (must be “AnalogInterpolated” encoder): (-8)
- Checks parameter value: (-17)
- Checks positioner name: (-18)
Description
This function gets the current Position Compare AquadB interpolation factor.
The predefined PCO interpolation values are the following:
4.
16.
256.
4096.
65536.
Prototype
int PositionerPositionCompareAquadBPrescalerGet(
int SocketID,
char PositionerName,
double * PCOInterpolationFactor
)
Input parameters
SocketID int Socket identifier gets by the
TCP_ConnectToServer” function.
PositionerName int Positioner name.
Output parameters
PCOInterpolationFactor double * Current PCO interpolation factor.
Return (In addition to the results of “Input Tests Common to all XPS
Functions”)
0: No error.
-8: Wrong object type for this command.
-17: Parameter out of range or incorrect.
-18: Positioner name doesn't exist or unknown command.
407 EDH0373En1023 01/18

Table of Contents

Other manuals for Newport XPS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Newport XPS and is the answer not in the manual?

Newport XPS Specifications

General IconGeneral
Controller TypeMulti-axis motion controller
Power Supply24 VDC
Communication InterfaceEthernet
Programming LanguageC, C++, .NET, LabVIEW
Supported Motor TypesStepper
Operating System CompatibilityWindows
AxesUp to 8 axes

Related product manuals