Defining the Over/Under Temperature Thresholds
Use this setting to define the maximum/minimum temperature offsets from
any heated zone set point before the system goes into an Alert condition. If
the condition is not resolved within 2 minutes, the system goes into a Fault
condition.
1. Log into your BBconn Cloud account, then do the following:
S Select SETUP TOOL - create or load a .NOR file.
S Select SYSTEM SETTINGS | TEMPERATURE.
2. Select Over Temperature Threshold, and enter the maximum
temperature offset above any heated zone before receiving an Over
Temperature alarm. The default is 15_ C (27_ F), the minimum is 5_ C
(10_ F), and the maximum is 61_ C (110_ F).
3. Select Under Temperature Threshold, and enter the maximum
temperature offset below any heated zone before receiving an Under
Temperature alarm. The default is 25_ C (45_ F), the minimum is 9_ C
(10_ F), and the maximum is 60_ C (110_ F).
4. When done, select SAVE.