SETUP TOOL
LOAD FROM USB/COMPUTER
USE PREVIOUS FILE
CREATE NEW
Please select how to load a configuration file
NETWORKING
SYSTEM SETTINGS
ProBlue Flex OEM User’s Guide
77
Part 1129255_01
E 2020 Nordson Corporation
Defining PLC Communications
Profinet, Ethernet/IP and Modbus TCP are natively supported and do not
require you to install a communication card.
S Refer to Connecting Profinet, Ethernet IP and Mod BUS/TCP for
more information.
S For all other communication cards, refer to documentation that came with
the communication kit for installation and setup instructions. You can also
get the appropriate instruction sheet for your communication card from
the BBconn Cloud Media Center.
Communication Kit Name Kit Part
Number
Instruction Kit
Part Number
KIT,ACCESS,PB
FLEX,COMM,PROFIBUS
1129161 1129124
KIT,ACCESS,PB
FLEX,COMM,ETHERCAT
1129162 1129293
KIT,ACCESS,PB
FLEX,COMM,CCLINK
1129163 1129294
KIT,ACCESS,PB
FLEX,COMM,SERCOS III
1129164 1129295
KIT,ACCESS,PB
FLEX,COMM,DEVICENET
1129165 1129296
KIT,ACCESS,PB
FLEX,COMM,POWERLINK
1129166 1129297
KIT,ACCESS,PB
FLEX,COMM,CCLINK IE
1129167 1129298
1. Log into your BBconn Cloud account, then do the following:
S Select SETUP TOOL - create or load a .NOR file.
S Select SYSTEM SETTINGS | NETWORKING | SPECIFIC
NETWORK.
2. Do the following to continue:
S For Profinet, enter the Profinet Station Name - the Profinet device name.
The default name is pbflex-pnio.
S The Profinet station name must follow these guidelines:
‐ Can contain letters and numbers
‐ Letters must be lower case
‐ Can contain a hyphen (-) or a period (.)
‐ Cannot begin or end with a hyphen (-)
‐ Cannot begin with the character string "port-xyz" (x, y, z = 0 to 9)
‐ Cannot have the form of an IP address n.n.n.n (n = 0 - 255)
3. When done, select SAVE.