4-99
4-2 Function Mode
4
Functions
10A6h
Allowable momentary power
interruption time
b002 R/W 3 to 250 0.1 [s]
10A7h Retry wait time b003 R/W 3 to 1000 0.1 [s]
10A8h
Momentary power
interruption/undervoltage
trip during stop selection
b004 R/W
00: Disabled
01: Enabled
10A9h
Momentary power
interruption retry time
selection
b005 R/W
00: 16 times
01: No limit
1170h
Starting frequency at
frequency pull-in restart
b011 R/W
00: Frequency at interruption
01: Max. frequency
02: Set frequency
10ADh Electronic thermal level b012 R/W
2000 to 10000
Set the rated current to 10000
0.01 [%]
1527h 2nd electronic thermal level b212 R/W
10AEh
Electronic thermal
characteristics selection
b013 R/W
00: Reduced torque characteristics 1
01: Constant torque characteristics
02: Reduced torque characteristics 2
1528h
2nd electronic thermal
characteristics selection
b213 R/W
10B5h Overload limit selection b021 R/W 00: Disabled
01: Enabled in acceleration/constant
speed operation
02: Enabled in constant speed operation
1529h 2nd overload limit selection b221 R/W
10B6h Overload limit level b022 R/W
2000 to 15000
Set the rated current to 10000
0.01 [%]
152Ah 2nd overload limit level b222 R/W
10B7h Overload limit parameter b023 R/W
1 to 300 0.1 [s]
152Bh 2nd overload limit parameter b223 R/W
10BBh
Overload limit source
selection
b028 R/W
00: Set values in b022
01: Input FV terminal
152Ch
2nd overload limit source
selection
b228 R/W
00: Set values in b222
01: Input FV terminal
1171h
Deceleration rate constant at
frequency pull-in restart
b029 R/W 1 to 30000 0.1 [s]
1172h
Frequency pull-in restart
level
b030 R/W 200 to 20000 0.01 [%]
Register
No.
Function name
Parameter
No.
R/W
Function
Monitor or data range
Resolution