4-104
4-2 Function Mode
4
Functions
1153h Output terminal P1 ON delay C144 R/W 0 to 1000
0.1 [s]
1154h
Output terminal P1 OFF
delay
C145 R/W 0 to 1000
1157h Relay output ON delay C148 R/W 0 to 1000
1158h Relay output OFF delay C149 R/W 0 to 1000
1165h Motor capacity selection H003 R/W
00: 0.2/02: 0.4/04: 0.75/
06: 1.5/07: 2.2/09: 3.7/
11: 5.5/12: 7.5
⎯
1541h 2nd motor capacity selection H203 R/W
00: 0.2/02: 0.4/04: 0.75/
06: 1.5/07: 2.2/09: 3.7/
11: 5.5/12: 7.5
⎯
1166h Motor pole number selection H004 R/W 2/4/6/8 1 [pole]
1542h
2nd motor pole number
selection
H204 R/W 2/4/6/8 1 [pole]
1168h Stabilization parameter H006 R/W 0. to 255. 1. [%]
1544h 2nd stabilization parameter H206 R/W 0. to 255. 1. [%]
0900h Enter command ⎯ W Indefinite value ⎯
Register
No.
Function name
Parameter
No.
R/W
Function
Monitor or data range
Resolution