App-2
Appendix-1 Parameter List
Appendix
* 2nd function is displayed when SET(08) is allocated to one of from C001 to C005.
Extended function mode
d102 DC voltage monitor 0.0 to 999.9 ⎯⎯V
d104
Electronic thermal
monitor
0.0 to 100.0 ⎯⎯%
F001
Output frequency
setting/monitor
Starting frequency to 1st or 2nd max.
frequency
⎯ Yes Hz
F002 Acceleration time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3000.
10.0 Yes s
F202
*2nd acceleration
time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3000.
10.0 Yes s
F003 Deceleration time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3000.
10.0 Yes s
F203
*2nd deceleration
time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3000.
10.0 Yes s
F004
Operator rotation
direction selection
00: Forward
01: Reverse
00 No ⎯
Parameter
No.
Name
Monitor or data range
(Digital Operator)
Default
setting
Changes
during
operation
Unit
Set
value
Parameter
No.
Function name
Monitor or data range
(Digital Operator)
Default
setting
Changes
during
operation
Unit
Set
value
Basic setting
A001
Frequency
reference
selection
00: Digital Operator (FREQ adjuster)
01: Terminal
02: Digital Operator (F001)
03: ModBus communication
10: Frequency operation result
00 No ⎯
A201
*2nd frequency
reference
selection
00 No ⎯
A002
RUN command
selection
01: Terminal
02: Digital Operator
03: ModBus communication
02 No ⎯
A202
*2nd RUN
command
selection
02 No ⎯
A003 Base frequency 30. to Max. frequency [A004] 60.
No Hz
A203
*2nd base
frequency
30. to Max. frequency [A204] 60.
A004
Maximum
frequency
30. to 400.
60.
No Hz
A204
*2nd maximum
frequency
60.
* 2nd control is displayed when SET (08) is allocated to one of from C001 to C005.