3-22
3-7 Parameter List
3
Operation
Analog input
A005 FV/FI selection
02: Switches between FV/FREQ adjuster via
terminal AT
03: Switches between FI/FREQ adjuster via
terminal AT
04: FV input only
05: FI input only
02 No ⎯ 4-9
A011 FV start frequency 0.0 to Max. frequency 0.0 No Hz 4-10
A012 FV end frequency 0.0 to Max. frequency 0.0 No Hz 4-10
A013 FV start ratio 0. to 100. 0. No % 4-10
A014 FV end ratio 0. to 100. 100. No % 4-10
A015 FV start selection
00: External start frequency (A011 set value)
01: 0 Hz
01 No ⎯ 4-10
A016 FV, FI sampling 1. to 17. 8. No ⎯ 4-11
Multi-step speed, Jogging
A020
Multi-step speed
reference 0
0.0/Starting frequency to Max. frequency 6.0 Yes Hz 4-11
A220
*2nd multi-step
speed reference 0
0.0/Starting frequency to 2nd max. frequency 6.0 Yes Hz 4-11
Parameter
No.
Function name
Monitor or data range
(Digital Operator)
Default
setting
Changes
during
operation
Unit Page
* 2nd control is displayed when SET (08) is allocated to one of from C001 to C005.