3-27
3-7 Parameter List
3
Operation
External frequency adjustment
A101 FI start frequency 0.0 to 400.0 0.0 No Hz
4-10
4-25
A102 FI end frequency 0.0 to 400.0 0.0 No Hz
4-10
4-25
A103 FI start ratio 0. to 100. 0. No %
4-10
4-25
A104 FI end ratio 0. to 100. 100. No %
4-10
4-25
A105 FI start selection
00: Use FI start frequency [A101]
01: 0 Hz start
01 No
4-10
4-25
Operation frequency
A141
Operation
frequency input A
setting
00: Digital Operator (F001)
01: Digital Operator (FREQ adjuster)
02: Input FV
03: Input FI
04: RS485 communication
01 No 4-26
A142
Operation
frequency input B
setting
02 No 4-26
A143 Operator selection
00: Addition (A + B)
01: Subtraction (A - B)
02: Multiplication (A × B)
00 No 4-26
Frequency addition
A145
Frequency
addition amount
0.0 to 400.0 0.0 Yes Hz 4-26
A146
Frequency
addition direction
00: Adds A145 value to output frequency
01: Subtract A145 value from output
frequency
00 No 4-26
VR adjustment
A151 VR start frequency 0.0 to 400.0 0.0 No Hz
4-10
4-27
A152 VR end frequency 0.0 to 400.0 0.0 No Hz
4-10
4-27
A153 VR start ratio 0. to 100. 0. No %
4-10
4-27
A154 VR end ratio 0. to 100. 100. No %
4-10
4-27
A155 VR start selection
00: Use VR start frequency [A151]
01: 0 Hz start
01 No
4-10
4-27
Parameter
No.
Function name
Monitor or data range
(Digital Operator)
Default
setting
Changes
during
operation
Unit Page
* 2nd control is displayed when SET (08) is allocated to one of from C001 to C005.