3-34
3-7 Parameter List
3
Operation
Communication function adjustment
C070
Operator/ModBus
selection
02: Digital Operator
03: ModBus
02 No
4-79
C071
Communication
speed selection
(Baud rate
selection)
04: 4800 bps
05: 9600 bps
06: 19200 bps
04 No
C072
Communication
station No.
selection
1. to 32. 1. No
C074
Communication
parity selection
00: No parity
01: Even
02: Odd
00 No
4-79
C075
Communication
stop bit selection
1: 1-bit
2: 2-bit
1No
C076
Communication
error selection
00: Trip
01: Trip after deceleration stop
02: Ignore
03: Free run
04: Deceleration stop
02 No
C077
Communication
error timeout
0.00 to 99.99 0.00 No s
C078
Communication
wait time
0. to 1000. 0. No ms
Various adjustment
C081 FV adjustment 0.0 to 200.0 100.0 Yes % 4-74
C082 FI adjustment 0.0 to 200.0 100.0 Yes % 4-74
Parameter
No.
Function name
Monitor or data range
(Digital Operator)
Default
setting
Changes
during
operation
Unit Page
* 2nd control is displayed when SET (08) is allocated to one of from C001 to C005.