302
PLC Setup Section 7-1
Parity
Baud Rate
Send Delay
Programming 
Console address
Settings Function Related 
flags and 
words
When set-
ting is read 
by CPU Unit
Word Bit(s)
+160 00 to 01 00 Hex: Even
01 Hex: Odd
10 Hex: None
Default: 00
This setting is valid only in no-protocol com-
munications mode. Set the Standard/Cus-
tom setting (word 160, bit 15) to 1 to enable 
this setting. 
A61902
(RS-232C 
Port Settings 
Changing 
Flag)
At the next 
cycle.
(Also can be 
changed with 
STUP (237).)
Programming 
Console address
Settings Function Related 
flags and 
words
When set-
ting is read 
by CPU Unit
Word Bit(s)
+161 00 to 07 00 Hex: 9,600 bps
01 Hex: 300 bps
02 Hex: 600 bps
03 Hex: 1,200 bps
04 Hex: 2,400 bps
05 Hex: 4,800 bps
06 Hex: 9,600 bps
07 Hex: 19,200 bps
08 Hex: 38,400 bps
09 Hex: 57,600 bps
0A Hex: 115,200 bps
Default: 00 Hex
This setting is valid only in no-protocol com-
munications mode. Set the Standard/Cus-
tom setting (word 160, bit 15) to 1 to enable 
this setting. 
A61902
(RS-232C 
Port Settings 
Changing 
Flag)
At the next 
cycle.
(Also can be 
changed with 
STUP (237).)
Programming 
Console address
Settings Function Related 
flags and 
words
When set-
ting is read 
by CPU Unit
Word Bit(s)
+162 00 to 15 0000 to 270F Hex (0 
to 99,990 ms)
Unit: 10 ms
Default: 0000
When the TXD(236) instruction is executed, 
data will be sent from the RS-232C after the 
send delay set here has expired. 
A61902
(RS-232C 
Port Settings 
Changing 
Flag)
At the next 
cycle.
(Also can be 
changed with 
STUP (237).)