303
PLC Setup Section 7-1
Start Code/End Code
Serial Gateway Settings
Communications Settings
Mode: Communications Mode
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+164 8 to 15 00 to FF
Default: 00
Start code: Set this start code only when the
start code is enabled (1) in bits 12 to 15 of
165.
A61902
(RS-232C
Port Settings
Changing
Flag)
At the next
cycle.
(Also can be
changed with
STUP (237).)
0 to 7 00 to FF
Default: 00
End code: Set this end code only when the
end code is enabled (1) in bits 8 to 11 of
165.
+165 12 0: None
1: Code in 164
Default: 0
Start code setting:
A setting of 1 enables the start code in 164
bits 8 to 15.
8 to 9 0: None
1: Code in 164
2: CR+LF
Default: 0
End code setting:
With a setting of 0, the amount of data being
received must be specified. A setting of 1
enables the end code in bits 0 to 7 of 164. A
setting of 2 enables an end code of CR+LF.
0 to 7 00: 256 bytes
01 to FF:
1 to 255 bytes
Default: 00
Set the data length to be sent and received
with no-protocol communications. The end
code and start code are not included in the
data length.
Set this value only when the end code set-
ting in bits 8 to 11 of 165 is “0: None.
This setting can be used to change the
amount of data that can be transferred at
one time by TXD(236) or RXD(235). The
default setting is the maximum value of 256
bytes.
Programming
Console address
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
+160 15 0: Default (stan-
dard)*
1: PLC Setup (cus-
tom)
Default: 0
*The default settings are for a baud rate of
9,600 bps.
A61901
(RS-232C
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Programming
Console address
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
+160 8 to 11 9: Serial Gateway
Default: 0
This setting determines whether the com-
munications mode for the RS-232C port
port.
The peripheral bus mode is used for all Pro-
gramming Devices except for Programming
Consoles.
A61901 (RS-
232C Port
Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)