304
PLC Setup Section 7-1
Data Bits
Stop Bits
Parity
Baud Rate (bps)
Programming
Console address
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
+160 3 0: 7 bits
1: 8 bits
Default: 0
These settings are valid when the RS-232C
Port Settings Selection is set to 1: PLC
Setup.
A61901
(RS-232C
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Programming
Console address
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
+160 2 0: 2 bits
1: 1 bit
Default: 0
These settings are valid when the RS-232C
Port Settings Selection is set to 1: PLC
Setup.
A61901
(RS-232C
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Programming
Console address
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
+160 0 to 1 00: Even
01: Odd
10: None
Default: 00
These setting is valid only when the commu-
nications mode is set to Host Link.
These settings are also valid only when the
RS-232C Port Settings Selection is set to 1:
PLC Setup.
A61902
(RS-232C
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Programming
Console address
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
+161 0 to 7 00: 9,600
01: 300
02: 600
03: 1,200
04 2,400
05: 4,800
06: 9,600
07: 19,200
08: 38,400
09: 57,600
0A: 115,200
Default: 00
These setting is valid only when the commu-
nications mode is set to Host Link.
These settings are also valid only when the
RS-232C Port Settings Selection is set to 1:
PLC Setup.
A61902
(RS-232C
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)