397
Auxiliary Area Section 9-11
Simple Backup Write Capacity A397 If a write for a simple backup operation fails, A397 will con-
tain the Memory Card capacity that would have been
required to complete the write operation. The value is in
Kbytes. (This indicates that the Memory Card did not have
the specified capacity when the write operation was started.)
0001 to FFFF hex: Write error (value indicates required
capacity from 1 to 65,535 Kbytes).
A397 will be cleared to 0000 hex when the write is com-
pleted successfully for a simple backup operation.
Read-only
Program Replacement End
Code
A65000 to
A65007
Normal End (i.e., when A65014 is OFF)
01 hex: Program file (.OBJ) replaced.
Error End (i.e., when A65014 is ON)
00 hex: Fatal error
01 hex: Memory error
11 hex: Write-protected
12 hex: Program replacement password error
21 hex: No Memory Card
22 hex: No such file
23 hex: Specified file exceeds capacity (memory error).
31 hex: One of the following in progress:
File memory operation
User program write
Operating mode change
Read-only
Replacement Error Flag A65014 ON when the Replacement Start Bit (A65015) has been
turned ON to replace the program, but there is an error. If
the Replacement Start Bit is turned ON again, the Replace-
ment Error Flag will be turned OFF.
Read/write
Replacement Start Bit A65015 Program replacement starts when the Replacement Start Bit
is turned ON if the Program Password (A651) is valid (A5A5
hex). Do not turn OFF the Replacement Start Bit during pro-
gram replacement.
When the power is turned ON or program replacement is
completed, the Replacement Start Bit will be turned OFF,
regardless of whether replacement was completed normally
or in error.
It is possible to confirm if program replacement is being exe-
cuted by reading the Replacement Start Bit using a Pro-
gramming Device, PT, or host computer.
Read/write
Name Address Description Access