398
Auxiliary Area Section 9-11
Program Error Information
Program Password A651 Input the password to replace a program.
A5A5 hex: Replacement Start Bit (A65015) is enabled.
Any other value: Replacement Start Bit (A65015) is dis-
abled.
When the power is turned ON or program replacement is
completed, the Replacement Start Bit will be turned OFF,
regardless of whether replacement was completed normally
or in error.
Read/write
Program File Name A654 to
A657
When program replacement starts, the program file name
will be stored in ASCII. File names can be specified up to
eight characters in length excluding the extension.
File names are stored in the following order: A654 to A657
(i.e., from the lowest word to the highest), and from the high-
est byte to the lowest. If a file name is less than eight charac-
ters, the lowest remaining bytes and the highest remaining
word will be filled with spaces (20 hex). Null characters and
space characters cannot be used within file names.
Example: File name is ABC.OBJ
Read/write
Name Address Description Access
Program Error Flag
(Fatal error)
A40109 ON when program contents are incorrect. CPU Unit opera-
tion will stop.
Read-only
Program Error Task A294 Provides the type and number of the tack that was being
executed when program execution stops as a result of a pro-
gram error.
Read-only
Name Address Description Access

Table of Contents