413
Auxiliary Area Section 9-11
Auxiliary Area Flags and Bits for Built-in Inputs
The following tables show the Auxiliary Area words and bits that are related to
the CJ1M CPU Unit's built-in inputs. These allocations apply to CPU Units
equipped with the built-in I/O only.
■ Interrupt Inputs
Name Address Description Read/Write Times when data is 
accessed
Interrupt Counter 0 
Counter SV
A532 Used for interrupt input 0 in counter mode.
Sets the count value at which the interrupt task 
will start. Interrupt task 140 will start when inter-
rupt counter 0 has counted this number of 
pulses.
Read/Write • Retained when 
power is turned 
ON.
• Retained when 
operation starts.
Interrupt Counter 1 
Counter SV
A533 Used for interrupt input 1 in counter mode.
Sets the count value at which the interrupt task 
will start. Interrupt task 141 will start when inter-
rupt counter 1 has counted this number of 
pulses.
Read/Write
Interrupt Counter 2 
Counter SV
A534 Used for interrupt input 2 in counter mode.
Sets the count value at which the interrupt task 
will start. Interrupt task 142 will start when inter-
rupt counter 2 has counted this number of 
pulses.
Read/Write
Interrupt Counter 3 
Counter SV
A535 Used for interrupt input 3 in counter mode.
Sets the count value at which the interrupt task 
will start. Interrupt task 143 will start when inter-
rupt counter 3 has counted this number of 
pulses.
Read/Write
Interrupt Counter 0 
Counter PV
A536 These words contain the interrupt counter PVs 
for interrupt inputs operating in counter mode.
In increment mode, the counter PV starts incre-
menting from 0. When the counter PV reaches 
the counter SV, the PV is automatically reset to 
0.
In decrement mode, the counter PV starts dec-
rementing from the counter SV. When the 
counter PV reaches the 0, the PV is automati-
cally reset to the SV.
Read/Write • Retained when 
power is turned 
ON.
• Cleared when 
operation starts.
• Refreshed when 
interrupt is gener-
ated.
• Refreshed when 
INI(880) instruc-
tion is executed.
Interrupt Counter 1 
Counter PV
A537 Read/Write
Interrupt Counter 2 
Counter PV
A538 Read/Write
Interrupt Counter 3 
Counter PV
A539 Read/Write