557
Specifications of Basic I/O Units Appendix A
CJ1W-MD232 DC Input/Transistor Output Unit
(MIL Connector, 16 inputs/16 Outputs, Sourcing)
Note The ON response time will be 20 µs maximum and OFF response time will be 400 µs maximum even if
the response times are set to 0 ms due to internal element delays.
Circuit Configuration
Output section (CN1) Input section (CN2)
Rated Voltage 24 V DC Rated Input Voltage 24 V DC
Operating Input Volt-
age
20.4 to 26.4 V DC
Operating Load Volt-
age Range
20.4 to 26.4 V DC Input Impedance 3.3 k
Maximum Load Cur-
rent
0.5 A/point, 2.0 A/Unit Input Current 7 mA typical (at 24 V DC)
Leakage Current 0.1 mA max. ON Voltage/ON Cur-
rent
14.4 V DC min./3 mA min.
Residual Voltage 1.5 V max. OFF Voltage/OFF
Current
5 V DC max./1 mA max.
ON Response Time 0.5 ms max. ON Response Time 8.0 ms max. (Can be set to between
0 and 32 in the PLC Setup.) (See
note.)
OFF Response Time 1.0 ms max.
Load Short-circuit
Protection
Detection current: 0.7 to 2.5 A min.
Automatic restart after error clear-
ance. (Refer to page 590.)
OFF Response Time 8.0 ms max. (Can be set to between
0 and 32 in the PLC Setup.) (See
note.)
No. of Circuits 16 (16 points/common, 1 circuit) No. of Circuits 16 (16 points/common, 1 circuit)
External Power Sup-
ply
20.4 to 26.4 V DC, 40 mA min. Number of Simulta-
neously ON Points
75% (at 24 V DC)
Insulation Resistance 20 M between the external terminals and the GR terminal (at 100 V DC)
Dielectric Strength 1,000 V AC between the external terminals and the GR terminal for 1 minute at a leakage current
of 10 mA max.
Internal Current Con-
sumption
5 V DC 130 mA max.
Weight 100 g max.
Accessories None
470
COM1
IN00
IN07
3.3 k
1000 pF
470
COM1
IN08
IN15
3.3 k
1000 pF
COM0(+V)
0 V
COM0(+V)
0 V
CN2(IN)
CN1(OUT)
ERR indicator
Output indicator
Internal circuits
Input indicator
to
to
OUT00
to
OUT07
OUT08
to
OUT15
Internal circuits
Load short-circuit
protected
Load short-circuit
protected

Table of Contents