556
Specifications of Basic I/O Units Appendix A
Terminal Connections
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate if
polarity is reversed.
• Be sure to wire both terminals 3 and 4 (COM0 (0 V)) of CN1.
• Be sure to wire both terminals 1 and 2 (+V) of CN1.
• Be sure to wire both terminals 3 and 4 (COM1) of CN2, and set the same polarity for both pins.
0
2
4
6
8
10
12
14
16
18
0204060
(°C)
Number of Simultaneously ON Points vs.
Ambient Temperature Characteristic
Number of simultaneously ON points
Ambient Temperature
Input voltage: 24 V DC
Input voltage: 26.4 V DC
12 points at 55°C
9 points at 55°C
16 points at 33°C 16 points at 45°C
12 to
24 V DC
24 V DC
COM0 (0 V)
1
3
5
7
9
11
13
15
15
14
13
12
11
10
09
08
17
19
+V
2
4
6
8
10
12
14
16
18
06
05
04
03
02
01
00
07
20
+V
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
20
18
16
14
12
10
8
6
4
2
19
17
15
13
11
9
7
06
05
04
03
02
01
00
07
5
3
1
15
14
13
12
11
10
09
08
COM1
NC
COM1
NC
COM0 (0 V)
CN1 (Outputs)
I/O word "m"
CN2 (Inputs)
I/O word "m+1"