627
Auxiliary Area Appendix C
Addresses Name Function Settings Status
after
mode
change
Status at
startup
Write timing/
Related Flags,
Settings
Word Bit
A597 --- DR00 Out-
put for Back-
ground
Execution
When a data register is specified as
the output for an instruction pro-
cessed in the background, A597
receives the output instead of DR00.
0000 to FFFF
hex
Cleared Cleared Not supported by
CJ1@-CPU@@ CPU
Units
A598 A59800 FPD Teach-
ing Bit
Turn this bit ON to set the monitoring
time automatically with the teaching
function.
While A59800 is ON, FPD(269) mea-
sures how long it takes for the diag-
nostic output to go ON after the
execution condition goes ON. If the
measured time exceeds the monitor-
ing time, the measured time is multi-
plied by 1.5 and that value is stored
as the new monitoring time.
(The teaching function can be used
only when a word address has been
specified for the monitoring time
operand.)
1: Teach moni-
toring time
0: Teaching
function off
Cleared Cleared ---
A59801 Equals Flag
for Back-
ground Exe-
cution
Turns ON if matching data is found
for an SRCH(181) instruction exe-
cuted in the background.
1: Search data
found in table
0: Search data
not found
Cleared Cleared Not supported by
CJ1@-CPU@@ CPU
Units
A600 to
A603
Macro Area
Input Words
When MCRO(099) is executed, the
contents of the four specified source
words (starting from the 1st input
parameter word) are copied here.
The contents of the four copied
words are then passed to the sub-
routine.
Input data:
4 words
Cleared Cleared ---
A604 to
A607
Macro Area
Output
Words
After the subroutine specified in
MCRO(099) has been executed, the
results of the subroutine are trans-
ferred from A604 through A607 to
the specified destination words. (out-
put parameter words)
Output data:
4 words
Cleared Cleared ---
A619 A61901 Peripheral
Port Set-
tings Chang-
ing Flag
ON while the peripheral port’s com-
munications settings are being
changed. This flag will be turned ON
when STUP(237) is executed and it
will be turned OFF after the settings
have been changed.
1: Changing
0: Not chang-
ing
Retained Cleared ---
A61902 RS-232C
Port Set-
tings Chang-
ing Flag
ON while the RS-232C port’s com-
munications settings are being
changed. This flag will be turned ON
when STUP(237) is executed and it
will be turned OFF after the settings
have been changed.
1: Changing
0: Not chang-
ing
Retained Cleared ---
A620 A62001 Communica-
tions Unit 0,
Port 1 Set-
tings Chang-
ing Flag
The corresponding flag will be ON
when the settings for that port are
being changed.
The flag will be turned ON when
STUP(237) is executed and it will be
turned OFF by an event issued from
the Serial Communications Unit after
the settings have been changed.
It is also possible for the user to indi-
cate a change in serial port settings
by turning these flags ON.
1: Changing
0: Not chang-
ing
Retained Cleared ---
A62002 Communica-
tions Unit 0,
Port 2 Set-
tings Chang-
ing Flag
1: Changing
0: Not chang-
ing
Retained Cleared ---
A62003 Communica-
tions Unit 0,
Port 3 Set-
tings Chang-
ing Flag
1: Changing
0: Not chang-
ing
Retained Cleared ---
A62004 Communica-
tions Unit 0,
Port 4 Set-
tings Chang-
ing Flag
1: Changing
0: Not chang-
ing
Retained Cleared ---