626
Auxiliary Area Appendix C
Note 1. CJ1M CPU Units with built-in I/O only.
2. These Auxiliary Area bits/words are not to be written by the user. The number of resends and re-
sponse monitoring time must be set by the user in the FB communications instructions settings in the
PLC Setup, particularly when using function blocks from the OMRON FB Library to execute FINS
messages or DeviceNet explicit messages communications. The values set in the Settings for
OMRON FB Library in the PLC Setup will be automatically stored in the related Auxiliary Area words
A580 to A582 and used by the function blocks from the OMRON FB Library.
A540
(See
note 1.)
A54000 Pulse Out-
put 0 Reset
Bit
The pulse output 0 PV (contained in
A276 and A277) will be cleared when
this bit is turned from OFF to ON.
--- Retained Cleared ---
A54008 Pulse Out-
put 0 CW
Limit Input
Signal Flag
This is the CW limit input signal for
pulse output 0, which is used in the
origin search. To use this signal,
write the input from the actual sensor
as an input condition in the ladder
program and output the result to this
flag.
--- ---
A54009 Pulse Out-
put 0 CCW
Limit Input
Signal Flag
This is the CCW limit input signal for
pulse output 0, which is used in the
origin search. To use this signal,
write the input from the actual sensor
as an input condition in the ladder
program and output the result to this
flag.
--- ---
A541
(See
note 1.)
A54100 Pulse Out-
put 1 Reset
Bit
The pulse output 1 PV (contained in
A278 and A279) will be cleared when
this bit is turned from OFF to ON.
--- Retained Cleared ---
A54108 Pulse Out-
put 1 CW
Limit Input
Signal Flag
This is the CW limit input signal for
pulse output 1, which is used in the
origin search. To use this signal,
write the input from the actual sensor
as an input condition in the ladder
program and output the result to this
flag.
--- ---
A54109 Pulse Out-
put 1 CCW
Limit Input
Signal Flag
This is the CCW limit input signal for
pulse output 1, which is used in the
origin search. To use this signal,
write the input from the actual sensor
as an input condition in the ladder
program and output the result to this
flag.
--- ---
A580
(See
note 2.)
A58000
to
A58003
FB Commu-
nications
Instruction
Retries
Automatically stores the number of
retries in the FB communications
instruction settings specified in the
PLC Setup.
0 to F hex As set in
PLC
Setup
Cleared Written at start of
operation
A581
(See
note 2.)
FB Commu-
nications
Instruction
Response
Monitoring
Time
Automatically stores the FB commu-
nications instruction response moni-
toring time set in the PLC Setup.
0001 to FFFF
hex (Unit: 0.1 s;
Range: 0.1 to
6553.5)
0000 hex: 2 s
As set in
PLC
Setup
Cleared Written at start of
operation
A582
(See
note 2.)
FB
DeviceNet
Communica-
tions
Instruction
Response
Monitoring
Time
Automatically stores the FB
DeviceNet communications instruc-
tion response monitoring time set in
the PLC Setup.
0001 to FFFF
hex (Unit: 0.1 s;
Range: 0.1 to
6553.5)
0000 hex: 2 s
As set in
PLC
Setup
Cleared Written at start of
operation
A595
and
A596
--- IR00 Output
for Back-
ground Exe-
cution
When an index register is specified
as the output for an instruction pro-
cessed in the background, A595 and
A596 receive the output instead of
IR00.
0000 0000 to
FFFF FFFF
hex
(A596 contains
the leftmost
digits.)
Cleared Cleared Not supported by
CJ1@-CPU@@ CPU
Units.
Addresses Name Function Settings Status
after
mode
change
Status at
startup
Write timing/
Related Flags,
Settings
Word Bit