Host Link Commands Section 6-3
Response Format An end code of 00 indicates normal completion.
Parameters Name, TC Number (Command)
In “Name,” specify the name of the instruction, in four characters, for changing
the SV. In “TC number,” specify the timer/counter number used for the instruc-
tion.
Operand, SV (Response)
In “Operand,” specify the name that indicates the SV classification. Specify
the name in four characters. In “SV,” specify either the word address where
the SV is stored or the constant SV.
6-3-20 SV CHANGE 3 –– W% (CQM1 Only)
Changes the contents of the second word of the TIM, TIMH(15), CNT, or
CNTR(12) at the specified program address in the user’s program. With this
command, program address can be specified for a program of more than 10K.
Command Format
@ W$ x 16
0
x 10
0
x 10
1
x 16
1
↵
Node no. Header
code
TerminatorFCSEnd code
Instruction name Classification
OP1 OP2 OP3 OP4
T I M (Space) TIMER
T I M H HIGH-SPEED TIMER
C N T (Space) COUNTER
C N T R REVERSIBLE COUNTER
Operand Classification Constant or word address
OP1 OP2 OP3 OP4 CQM1 PCs CPM1 PCs
C I O (Space) IR or SR 0000 to 0252 0000 to 0019
0200 to 0252
L R (Space) (Space) LR 0000 to 0063 0000 to 0015
H R (Space) (Space) HR 0000 to 0099 0000 to 0019
A R (Space) (Space) AR 0000 to 0027 0000 to 0015
D M (Space) (Space) DM 0000 to 6655 0000 to 1023
6144 to 6655
DM* (Space) DM (indirect) 0000 to 6655 0000 to 1023
6144 to 6655
C O N (Space) Constant 0000 to 9999 0000 to 9999
@ W%
OP4OP3OP2OP1
OP4OP3OP2OP1
x 10
2
x 10
0
x 10
1
x 10
5
x 10
4
x 10
3
x 10
0
x 10
3
x 10
2
x 10
1
x 10
1
x 10
0
x 10
2
x 10
3
x 10
1
x 10
0
*
↵
Node no. Program
address
Must be "0"
Name Timer/counter
(0000 to 0511)
TerminatorFCS
Header
code
Operand SV