113
Functionality for All Option Board's Section 7-1
This section provides examples of values for present errors and the error log
when the following errors occur.
Operation Log
This is a log of recorded operations. The operation details are given using the
following operation codes.
Sequence of
occurrence
Error description Unit Conduction Time at
error
Error status
1 Unsupported Option Board 0 day, 0 hours, 6 minutes =
000006 hex (minutes)
Cleared
2 Safety Input terminal error
detected in dual-channel
monitoring
100 days, 12 hours, 12 min-
utes = 02355C hex (minutes)
Error occurred
3 Output power supply voltage
error
100 days, 12 hours, 18 min-
utes = 023562 hex (minutes)
Error occurred
Present Error Error Log
Value Error code Value
+0 Error Information Map 0 00 hex +0 Record 1 Unit Con-
duction
Time at
error
22 hex
+1 Error Information Map 1 00 hex +1 02 hex
+2 Error Information Map 2 04 hex +2 35 hex
+3 Error Information Map 3 00 hex +3 62 hex
+4 Error Information Map 4 02 hex +4 Record 2 Error code 13 hex
+5 Error Information Map 5 00 hex +5 Unit Con-
duction
Time at
error
02 hex
+6 Error Information Map 6 00 hex +6 35 hex
+7 Error Information Map 7 00 hex +7 5C hex
+8 Error Information Map 8 00 hex +8 Record 3 Error code 3E hex
+9 Error Information Map 9 00 hex +9 Unit Con-
duction
Time at
error
00 hex
+10 Error Information Map 10 00 hex +10 00 hex
+11 Error Information Map 11 00 hex +11 06 hex
+12 Record 4
and
higher
00 hex
--- 00 hex
+39 00 hex
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Operation record 1 (most recent) operation code
+1 Operation record 1 (most recent) Unit Conduction Time third byte at operation
+2 Operation record 1 (most recent) Unit Conduction Time second byte at operation
+3 Operation record 1 (most recent) Unit Conduction Time first byte at operation
--- ---
+36 Operation record 10 (oldest) operation code
+37 Operation record 10 (oldest) Unit Conduction Time third byte at operation
+38 Operation record 10 (oldest) Unit Conduction Time second byte at operation
+39 Operation record 10 (oldest) Unit Conduction Time first byte at operation