60
Installation Section 4-1
Mounting Brackets
DIN Track
Secure the DIN Track to the control panel using M4 screws at interval of
210 mm or less (6 holes or fewer). The tightening torque is 1.2 N·m.
End Plates
Use the PFP-M End Plates to secure the Units so that they do not move
towards one end or the other of the DIN Track.
Mounting with Screws
1. Open mounting holes in the mounting surface according to the dimensions
diagram. 
2. Use M4 screws, which fit the holes on the G9SP-series Controller. The
tightening torque is 1.2 N·m.
4-1-4 Connecting Expansion I/O Units and Expansion Units
This section describes how to connect Expansion I/O Units and Expansion
Units.
Connection Methods
1,2,3... 1. Remove the cover from the G9SP-series Controller’s or the Expansion I/O
Unit’s expansion connector. Use a flat-head screwdriver to remove the cov-
er from the Expansion I/O Connector.
15
10
4.5
25
25
25
10
25
15
1000
1000 (500)*
PFP-100N2
PFP-100N/50N
15
10
4.5
25 25
25
10
25 15(5)*
1
16
1.51
29.2
24
27
28-25  × 4.5 long holes
30±0.3
7.3±0.15
35±0.3 27±0.15
*PFP-50N dimensions are given in parentheses.
Expansion Connector Cover
(1) Remove