145
Changing the Configuration Data Section 9-4
9-4 Changing the Configuration Data
This section describes how to change the G9SP-series Controller configura-
tion data after the configuration has been downloaded or after operation has
been started.
Procedure for Changing the Configuration
To change the G9SP-series Controller configuration data, first carefully check
system safety and then unlock the configuration data. The procedure for
changing the configuration is as follows:
1,2,3... 1. Check the system safety.
2. Change the G9SP-series Controller's operating mode from RUN to IDLE.
3. Unlock the G9SP-series Controller configuration data.
4. Download the configuration data to the G9SP-series Controller.
5. Verify the configuration data.
6. Change the G9SP-series Controller's operating mode from IDLE to RUN.
7. Perform safety validation testing (user testing).
8. Lock the configuration data.
Precautions for Safe Use
After changing the G9SP-series Controller's configuration data, confirm that
the safety functions are functioning properly before starting operation.