Installation Section 4-1
4-1 Installation
This section provides precautions on the environmental factors that must be
considered and the installation location of each G9SP-series Unit.
4-1-1 Installation Location
Installation Environment
Do not install the G9SP-series Controller in the following locations.
Locations subject to ambient temperatures lower than 0°C or higher than
55°C.
Locations subject to condensation as the result of severe changes in tem-
perature.
Locations subject to ambient humidity lower than 10% or higher than
90%.
Locations subject to corrosive or flammable gases.
Locations subject to excessive dust, salt, or metal filings.
Locations subject to direct shock or vibration.
Locations subject to direct sunlight.
Locations subject to water, oil, or chemicals.
Always enclose or protect the G9SP-series Controller sufficiently in the follow-
ing locations.
Locations subject to static electricity or other forms of noise.
Locations subject to strong electromagnetic fields.
Locations subject to possible exposure to radioactivity.
Locations close to power lines.
Installation in Control Panels
When the G9SP-series Controller is being installed in a control panel, be sure
to provide proper ambient conditions as well as access for operation and
maintenance.
Installation Orientation
When installing the G9SP-series Controller in a control panel, it must be
installed with the side with indicators and communications ports facing the
front to ensure proper heat dissipation.