133
Downloading Configuration Data to the G9SP-series Controller and Verification Section 8-2
8-2 Downloading Configuration Data to the G9SP-series
Controller and Verification
This section provides the procedure to place the G9SP Configurator online
and download configuration data to the G9SP-series Controller.
8-2-1 Connecting Online
Procedure
When an online connection is established, communications between the
G9SP Configurator and G9SP-series Controller will start.
1,2,3... 1. Click the Connect Icon ( ).
2. If the icon changes as shown below, communications have been start-
ed.
8-2-2 Downloading to G9SP-series Controller
Procedure
After the online connection has been established, there are two ways to down-
load configuration data to the G9SP-series Controller, as shown below.
1,2,3... 1. Click the Download Icon ( ).
2. Input the Device Password when prompted. If a device password is not set,
do not input anything.
3. If a display appears saying that the download was successful, the down-
load was completed normally.
Precautions for Correct Use
The configuration data cannot be downloaded while a Memory Cassette is
inserted in the G9SP-series Controller. If necessary, remove the Memory
Cassette, restart the G9SP-series Controller, and then download the data.