Precautions for Safe Use
Handling
Do not drop the G9SP-series Controller or subject it to excessive vibration or mechanical shock. The
G9SP-series Controller may be damaged and may not function properly.
Installation and Storage Environment
Do not use or store the G9SP-series Controller in any of the following locations:
Locations subject to direct sunlight
Locations subject to temperatures or humidity outside the range specified in the
specifications
Locations subject to condensation as the result of severe changes in temperature
Locations subject to corrosive or flammable gases
Locations subject to dust (especially iron dust) or salts
Locations subject to water, oil, or chemicals
Locations subject to shock or vibration
Take appropriate and sufficient measures when installing systems in the following locations. Inappropri-
ate and insufficient measures may result in malfunction.
Locations subject to static electricity or other forms of noise
Locations subject to strong electromagnetic fields
Locations subject to possible exposure to radioactivity
Locations close to power supplies
This is a class A product designed for use in industrial environments. In residential areas it may cause
radio interference, in which case the user may be required to take adequate measures to reduce interfer-
ence.
Installation and Mounting
Use the G9SP-series Controller within an enclosure with IP54 protection or higher according to IEC/
EN 60529.
Use DIN Track (TH35-7.5/TH35-15 according to IEC 60715) or M4 screws with a tightening torque of
1.2 N·m (10.5 lb·in) to install the G9SP-series Controller into the control panel.
Mount the G9SP-series Controller to the DIN Track using PFP-M End Plates (not included with the
G9SP-series Controller) to prevent it from falling off the DIN Track because of vibration. Correctly
mount all Units to DIN Track.
Install the G9SP-series Controller in the vertical direction shown below to ensure adequate cooling.
Space must be provided around the G9SP-series Controller, at least 20 mm from its side surfaces and
at least 50 mm from its top and bottom surfaces, for ventilation, wiring and Unit replacement.
Be sure to lock all locking mechanisms, such as those on I/O terminal blocks and connectors, before
attempting to use the G9SP-series Controller.

Table of Contents