143
Configuration Lock and Automatic Operation Section 9-3
9-3 Configuration Lock and Automatic Operation
Configuration Lock
The configuration data that was saved in the G9SP-series Controller can be
locked to protect the data after it has been downloaded, verified, and safety
validation testing (user testing) has been performed. Once the configuration is
locked, the configuration cannot be changed until it is unlocked.
The following occurs when the configuration lock is set.
The LOCK indicator on the front face of the G9SP-series Controller will
light yellow when the data is locked. (When unlocked, the indicator will
flash yellow.)
On the G9SP Configurator, the Verified [Locked] is displayed.
* After the data has been locked, the lock icon will turn yellow if the configura-
tion is changed.
Configuration Lock Procedure
1,2,3... 1. Go online and then click the Configuration Lock Icon.
2. Input the Device Password when prompted. If a device password is not set,
do not input anything.
3. The LOCK indicator on the front of the G9SP-series Controller will light yel-
low if the configuration is locked successfully. A mark that indicates the
locked status will be displayed on the G9SP Configurator.
Precautions for Correct Use
The configuration data must be verified before it can be locked. Confirm that
“Verified” is displayed on the G9SP Configurator.
Starting Operating Mode Using Automatic Operation
To protect the user, the G9SP-series Controller will always start in IDLE Mode
if safety validation testing (user testing) has not been completed.
After safety validation testing has been completed, the G9SP-series Control-
ler will start in RUN Mode if the following conditions are met. In that case, it
will not be necessary to change the mode from the G9SP Configurator.
The configuration is locked.
The power was turned OFF after changing to RUN Mode.
Precautions for Correct Use
Even if the configuration is locked, the G9SP-series Controller will not start in
RUN Mode the next time if the power is turned OFF while in IDLE Mode. Be
sure to turn OFF the power while in RUN Mode.