EasyManua.ls Logo

Omron G9SP-N20S - 10-2 Monitoring Programs

Omron G9SP-N20S
236 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
126
Ethernet Communications Section 7-3
7-3-2 Application Example
System Configuration
This section uses the following example to describe how to access the G9SP-
series Controller from a Standard PLC by performing Ethernet communica-
tions through an Ethernet Communications Board (CP1W-CIF41).
Note This example uses the following OMRON Standard PLC.
G9SP-series Controller Settings
Make the settings for TCP/IP in the system settings of the G9SP Configurator.
These settings are set in the G9SP-series Controller and Ethernet Option
Board when the configuration data is downloaded.
Product Model/version
CPU Unit (Standard PLC) CJ1M-CPU11
Ethernet Communications Unit CJ1W-ETN21
Switching hub W4S1-05B
Support Software (for setup and
creating ladder programs)
CX-Programmer Ver. 9.10
CJ1M
CJ1W-ETN21
Ethernet Unit
G9SP-series Controller
FINS/UDP
OMRON Standard PLC (See note.)
CP1W-CIF41
Option Board
192.168.250.1
192.168.250.2
Switching hub
Parameter Description Set value for this
example
IP address IP address of Ethernet Option Board.
Default value: 192.168.250.1
192.168.250.2
Subnet mask Subnet mask of Ethernet Option Board.
Default value: 255.255.255.0
No change is
required.
Default gateway Set the IP address of the default gate-
way. Default value: 0.0.0.0 (IP routing
not supported)
No change is
required.
FINS node address Set the FINS node address of the
Ethernet Option Board. If automatic
setting is specified, a value that
matches the rightmost byte of the IP
address is stored.
Default value: Automatic (matching the
rightmost byte of the IP address)
Setting range: 1 to 254
No change is
required.

Table of Contents

Related product manuals